Table 1

R-Value

 

A material’s R-value is the measure of its resistance to heat flow. It is important to know the R-value because many states or regions require that a roof system have a minimum amount of thermal resistance on commercial, industrial, and/or institutional buildings. The way it works is simple: the higher the R-value, the more the material insulates.

Material

Thickness In Inches

C-Value

R-Value

Metal

N/A

0.000

0.00

Concrete

1.0

3.333

0.30

Gypsum

1.0

1.667

0.60

Wood

1.0

1.099

0.91

Tectum

1.0

0.500

2.00

Inside Air Film

N/A

1.087

0.92

Outside Air Film - Summer

N/A

4.000

0.25

Outside Air Film - Winter

N/A

5.882

0.17

Vapour Retarders

N/A

0.000

0.00

BUR Gravel

N/A

2.941

0.34

BUR Smooth

N/A

4.167

0.24

Fibreboard

1.0

0.360

2.78

Perlite

1.0

0.360

2.78

Phenolic Foam*

1.0

0.120

8.30

Fibre Glass

1.0

0.256

3.90

Polyisocyanurate

1.0

0.180

5.56

Polyisocyanurate Composite

1.5

0.240

4.17

Polystyrene Bead Board

1.0

0.280

3.57

Polystyrene Composite Board

1.5

0.301

3.32

Polystyrene - Expanded (EPS)**

1.0

0.260

3.85

Polystyrene - Extruded (XEPS)***

1.0

0.200

5.00

Sprayed Polyurethane Foam****

1.0

0.150

6.88

Cork

1.0

0.280

3.57

EPDM

1.14

50.0

0.02

Some common roofing materials and their corresponding values for Thermal Conductance (C) and Thermal Resistance (R) are shown in the following table.

 

* Problems have been reported with regard to the use of Phenolic Foam roof insulation. Incidents of deck corrosion have been reported in cases where the insulation is in direct contact with steel roof decks and there is moisture present.

** Molded, Expanded Polystyrene Insulation, also referred to as MEPS, can have an R-value that will vary from less than 4.00 to slightly more than 4.00. The amount shown is an average amount used for roof system R-value calculations.

*** Extruded, Expanded Polystyrene Insulation is commonly used in Inverted Roof Membrane Assemblies (IRMA).

****Sprayed Polyurethane Foam (SPF) will have an R-Value of 7.14 when it is newly installed. After it ages a few months, the R-Value will reduce to somewhere around 6.88.

The C-value (C) is a measure of the Thermal Conductance of the material and is the reciprocal of R, or

Thermal conductivityC is determined only when the Thermal Conductivity (k) of a material is known.

Temperature lossThermal Conductivity is the measure of the amount heat that will be transmitted through a one inch (1") thick piece of homogenous material, one square foot (1 ft.2) in size, in one (1) hour, when there is a one degree Fahrenheit (1° F) temperature change. The equation for "k" is:

COMPONENT

R-VALUE

Inside Air Film

0.92

Steel Deck

0.00

2" Polyisocyanurate (5.56 * 2)

11.12

¾" Perlite (2.78 * 0.75)

2.09

Smooth Built-Up Roof

0.24

Outside Air Film in Winter

0.17

TOTAL

14.54

K Now let’s see how easy it is to figure the R-value. First of all, you need to know what the components of the roof system are. We’re going to figure the value of some common ones. Let’s assume the roof system consists of a smooth-surfaced built-up over ¾" of perlite coverboard over 2" polyisocyanurate insulation on a steel deck in the winter. The season makes a difference with the value of the outside air film. Let’s start from the inside and go out.

Rvalue

 

Total R-value for the above roof system is 14.54.

 

Although these pages are checked regularly and every care is taken with the information within. Delston can not accept any responsibility or liability for information or results displayed within due to third party interference. All information was deemed correct at time of publication.

Author Myrddin
Copyright © 1999 [Delston ]. All rights reserved.

 

 

 

 

 

 